Installation Instructions
variable, the probe should be close to the work area.
Some experimenting with probe location is often
needed to find its optimum position.
In a bath process, the addition of a stirrer will help
to eliminate thermal lags. Since the thermocouple
is
basically a point measuring device, putting more than
one thermocouple in parallel will provide an average
temperature reading and produce better results In air
heated processes.
NOTE:
if controls
with
“F”
or
"S”
outputs
drive loads
with grounded or hot input terminals (not floating), an
isolated
thermocouple must be used. Otherwise, when
both
input
and
output
are grounded, severe ground loop
currents will
result,
causing errors and permanent
controller damage.
Standard thermocouple limits of error are
± 4ºF
or
0.75%
(half that for special) plus drift caused by
improper protection or over temperature. This is far
greater than controller error, but can not be corrected
at the sensor except by selection and replacement. In
extreme case, total system requirements can be met by
offsetting the control to compensate for these outside
errors.
Operating Instructions
Control Panel Description
Continuous
Display Of
Process
Continuous
Display
Of
Setpoint
Or
Indexed
Parameter
Touch Key Group
Pressing
The
“I”
Button
Advances
The Cursor In The
“Index” Group
LED To
indicate
Output
“Status"
Function
Selected
Indicated
By LED
“Cursor”
Advanced By “I”
Button
Enters The
Selected
Value TO
Nonvolatile
Memory
Raises
(lncreases)
Lowers
The Selected
(Decreases) The
Variable
Selected Variable
12